GW1000-DHPEThe DataLink GW1000-DHPE is a gateway between an Ethernet TCP/IP Network and AB’s DH+ Network. This cost-efficient solution extends the life of legacy Allen-Bradley PLC5 and SLC/04s by eliminating the need to upgrade each PLC with an Ethernet processor.
The GW1000 hardware is a multi-protocol gateway that can easily be converted to several protocols with a firmware change (ie. DF1, ASCII, Modbus, ModTCP, AB Ethernet or Ethernet/IP to multiple DH+/DH-485) all for $1,250 USD list.
You may wish to program via RSLINX (AB Ethernet driver) remotely over Ethernet with our GW1000-ABEIP firmware or switch to RSLINX (1770-KF2 driver) serial DF1 to DH+ using our GW1000-DHP1 firmware.
In Ethernet mode, the GW1000 has the ability to communicate with 5 Ethernet connections simultaneously to DH+ (ie. up to 5 RSLINX workstations, SLC 5/05, Compactlogix etc. connections) .
For more details: Application Notes & User’s Manual
Digi Ethernet Chip & DF1 Driver: The GW1000-DHPE incorporates the Digi NS7520 Ethernet Chip on it’s board using the Digi’s Redirector software to create a tunnel over Ethernet TCP/IP for any existing serial com port DF1 driver. The beneifit of the GW1000 solution is that there isn’t any internal reformation of the serial DF1 protocol, thus eliminating a “BOTTLENECK” of an internal DF1 RS-232 link. The tunnelled packet is received by the GW1000 and directly formatted for DH+ transmission, and inversly, a DH+ received packet is immediately placed in an Ethernet TCP/IP packet for transmission to the Redirector software on the PC/HMI/MMI.
The DataLink GW1000 Controller enables users to run MMI applications or program/monitor PLCs & SLCs on a DH+ Network from an Ethernet LAN station. Tested applications include RSLinx,RSLogix,RSView, Wonderware, & Citect.
For details, pricing, or to find out if this solution is suitable for your application, please contact us.
Compact and Lightweight:
The smallest, portable freestanding Din Rail interface available.
Easy Configuration:
All parameters are menu-driven.
Cost efficient:
Reduces the need to purchase an AB Ethernet Processor for each PLC/SLC.
| Specifications: | |
| Physical Dimensions Size: 0.90″ H x 4.65″ D x 3.98″ W (22.8mm x 118.3mm x 101.0mm) Weight: 0.66lbs (0.3kg) Power: 9-27 VDC; Less than 2 WattsInstallation Plastic enclosure; Freestanding or DIN rail mounting with integrated clipEnvironment Operating: +32 F to 122 F (0C to +50 C) Storage: -40 F to +185 F (-40C to +85C) Humidity: 5% to 95% non-condensing Protocols A-B Channel: Allen-Bradley Data Highway Plus Ethernet Channel: TCP/IP – 100-Base-T Serial Channel: DF1 Communications A-B Channel: Synchronous, DH+ at 57.6, 115.2, and 230.4 Kbaud Ethernet Channel: 100-Base–T; TCP/IPSerial channel: |
Configuration Integrated web server for configuring communications parameters.Indicators Power DH+ status Serial Status Serial RX Serial TX Ethernet Activity Ethernet Link Pushbuttons Reset ConfigurationHardware Connections – Top - 3-pin power – 3.81mm pitch removable screw terminal plug - 3-pin A-B DH+ – 5.08mm pitch removable screw terminal plug - RJ45- EthernetConnections – Bottom - 5-pin RS485/RS422 – 3.81mm pitch removable screw terminal plug - D9 – RS232 port - USB |
The DataLink GW1000-DHPE is a gateway between an Ethernet TCP/IP Network and AB’s DH+ Network. This cost-efficient solution extends the life of legacy Allen-Bradley PLC5 and SLC/04s by eliminating the need to upgrade each PLC with an Ethernet processor.
Special Pricing in Effect! Order the GW1000 for just $1,250 USD List.

Call or email for any technical support issues or pricing inquiries
Toll free: (866) 286-2745
or (360) 306-5878

More About DataLink Technologies
Interfacing PC’s, SCADA Systems, AB PLC’s, SLC’s, computers, modems, variable speed drives and OEM equipment to Modicon’s Modbus, Allen-Bradley’s Data Highway Plus (DH+), DH-485, and Remote I/O. Interfacing Industrial Ethernet (Ethernet I/P, TCP/IP, Modbus TCPIP), Profibus, and DeviceNet protocols. See our complete product index and our best seller list.
copyright 2011 | All rights reserved | sitemap | Contact Us | (360) 306-5878 | Toll free (866) 286-2745
RSLINX | RSLOGIX | RIO | Ethernet/IP DH+ | SLC | PLC | MODBUS DH+ | INTERNAL SOLUTIONS | PRODUCTS | DH+ | DH-485 | 1770-KF2 | 1770-KF3 | 1784-KTX | 1784-PKTX | 1784-PCMK | SST-5136-SD | DF1 to DH+ | | DH+ to Ethernet | 1784-U2DHP | 1784-PKTX